WarmRite Injection Mixing Control Panel

The WarmRite Injection Mixing Control Panel is designed to control supply water
temperature by injection mixing. The WarmRite Control provides variable speed
operation of an injection circulator based on outdoor air temperature. This panel
is ideal when supply temperature control is required. The application of this
panel is extended to control the return water temperature for conventional boilers
by installing the return water temperature sensor.
When the control is in the outdoor reset mode, the speed of the injection circulator
is varied to maintain a target water temperature in the supply manifold based
on outdoor air temperature. The control can alternately be used as a set point
control. In this mode, the speed of the injection circulator is varied to maintain
a user adjustable supply fluid temperature. A room thermostat monitors the desired
room temperature and turns the mixing control off when the zone(s) is satisfied.
The WarmRite Injection Mixing Control Panel is operated as a single zone system
using the thermostat to activate the control. The secondary circulator operates
continuously providing even heat distribution during the heat up and cool down
cycles.
The control panel can be operated with subzones set up on a single zone panel.
The system thermostat is operating the main heat input while the subzone thermostats
operate the loops fitted with valve actuators. The sub zoning should not exceed
more than 50 percent of the loops.
The panel can be operated as a multiple zone system. The on/off valves located
on the supply manifold are fitted with optional electrical valve actuators to
control individual loops in the system. In this application, every actuator is
connected to a thermostat located in the area served by the loop. When the thermostat
calls for heat, the actuator opens the loop allowing flow. When all loops are
satisfied, the secondary circulator is shut down and the injection control is
disabled.
Note: Ensure that the thermostat is capable of handling the amperage draw from
the actuators (check manufacturer specifications).
Features:
- 5, 8 and 11 loop control panels allowing 3-11 loop systems
- Supply manifold with balancing valves
- Return manifold with on/off valves and flow control indicators
- WarmRite control (includes outdoor sensor and two universal sensors)
- Circulator control module (includes 24V transformer, circulator relay, dry
contact enable, and high limit) and excersisor
- Secondary circulator
- Injection circulator
- Pressure and temperature gauges
- Fill / drain valves
- Automatic air vent
- Isolating valves
- Steel Cabinet
- Fittings must be ordered separately from a choice of 3/8", 1/2",
5/8", 3/4" XPA or PEX. Thermostat is not included.
- Kitec General Help
- Kitec shipping / availability guidelines
Note: Quantities can be modified after you "Add to
Cart". The shopping cart will also give you a running total of the shipping
charges.
| Place Order |
5 Loop Warmrite Injection Mixing Control Panel
Accommodates 3-5 loops 489912 |
|
8 Loop Warmrite Injection Mixing Control Panel
Accommodates 6-8 loops 489915 |
|
11 Loop Warmrite Injection Mixing Control Panel
Accommodates 9-11 loops 489918 |
|


[Home] [Catalog]
[Contact Us] [Parts] [Review
Shopping Cart ] [About Us / Terms of Sale]
[Boilers] [Radiant
Heating] [Water Heaters] [Plumbing]
[Pumps] [Indoor Air
Quality] [Insulation]
Purchase products securely with:
Manufacturers may change product specifications and information without notice.
Copyright 2008, JupiterHeating.com
& Jupiter Sales, LLC. All rights reserved.
|